NP12-250Ah-T16

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 266 Ah (c20), Regulated Valve, high porosity pure virgin lead grid plate

Description

General Purpose Multi Cell Block battery, VRLA AGM, ABS case, 12V with (2) M8 threaded insert terminals [ WPC @10 min, 722.5 WPC @15 min to 1.67vpc] [242.4Ah (c8), 266Ah (c20)], 20.47″L x 10.55″W x 8.82″H (max ht), 159.5 Lbs

Additional information

Weight 159.5 lbs
Dimensions 20.47 × 10.55 × 8.82 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

high porosity pure virgin lead grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M8 threaded insert

Terminal Location

f

BCI Reference

8D

Length inches

20.47

Width inches

10.55

Height inches

8.82

Weight in Lbs

159.5

WPC (15min to 1.67vpc @ 25c)

722.5

240-cell kW rating (15min)

173.4

AH (c5)

220

AH (c8)

242.4

AH (c10)

252

AH (c20)

266

50% DOD Cycle rating

450

Capacity Bracket (15 Min WPC)

680 – 729 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

General Purpose