NP2-400Ah-T20

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 426 Ah (c20), Regulated Valve, high porosity pure virgin lead grid plate

Description

General Purpose Industrial Single Cell battery, VRLA AGM, ABS case, 2V with (4) M8 threaded insert terminals [956 WPC @15 min to 1.67vpc] [388.8Ah (c8), 426Ah (c20)], 8.27″L x 6.93″W x 14.41″H (max ht), 56.1 Lbs

Additional information

Weight 56.1 lbs
Dimensions 8.27 × 6.93 × 14.41 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

high porosity pure virgin lead grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

M8 threaded insert

Terminal Location

Top

Length inches

8.27

Width inches

6.93

Height inches

14.41

Weight in Lbs

56.1

WPC (15min to 1.67vpc @ 25c)

956

240-cell kW rating (15min)

229.44

AH (c5)

358

AH (c8)

388.8

AH (c10)

405

AH (c20)

426

50% DOD Cycle rating

825

Capacity Bracket (15 Min WPC)

915 – 989 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Capacity Bracket (C20 Ah)

350 – 499 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

General Purpose