Description
UPS High Rate Multi-Cell VRLA Battery, Lead Calcium AGM, ABS Resin case, 12V with (2) M5 threaded insert terminals [135 WPC @15 min to 1.67vpc],[33Ah (c20)], 7.76″L x 5.16″W x 6.22″H (max ht), 26.32 Lbs
Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 33 Ah (c20), Regulated Valve, lead calcium grid plate
UPS High Rate Multi-Cell VRLA Battery, Lead Calcium AGM, ABS Resin case, 12V with (2) M5 threaded insert terminals [135 WPC @15 min to 1.67vpc],[33Ah (c20)], 7.76″L x 5.16″W x 6.22″H (max ht), 26.32 Lbs
| Weight | 26.32 lbs |
|---|---|
| Dimensions | 7.76 × 5.16 × 6.22 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead-Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Case Material | ABS Resin |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94HB-Non-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | M5 threaded insert |
| Terminal Location | Top |
| Length inches | 7.76 |
| Width inches | 5.16 |
| Height inches | 6.22 |
| Weight in Lbs | 26.32 |
| WPC (10min to 1.67vpc @ 25c) | 172 |
| WPC (15min to 1.67vpc @ 25c) | 135 |
| WPC (20min to 1.67vpc @ 25c) | 105 |
| 240-cell kW rating (10min) | 41.28 |
| 240-cell kW rating (15min) | 32.4 |
| 240-cell kW rating (20min) | 25.2 |
| AH (c20) | 33 |
| Capacity Bracket (10 Min WPC) | 130 – 179 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 130 – 179 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 90 – 129 WPC (15 min) |
| Capacity Bracket (C20 Ah) | 20 – 49 Ah (C20) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | High-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Data Center UPS Systems |