Description
Telco Battery, VRLA AGM (frequent cycling), high modulus polyphenylene oxide case, 2V with (2) M8 Threaded Insert terminals [1442 WPC @15 min to 1.67vpc],[449.1Ah (c10), 442.2Ah (c8)], “L x 7.1″W x 6.3″H (max ht), 61 Lbs
Lead Acid AGM Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 442.2 Ah (c8), Regulated Valve, Thin Lead Calcium Grid plate
Telco Battery, VRLA AGM (frequent cycling), high modulus polyphenylene oxide case, 2V with (2) M8 Threaded Insert terminals [1442 WPC @15 min to 1.67vpc],[449.1Ah (c10), 442.2Ah (c8)], “L x 7.1″W x 6.3″H (max ht), 61 Lbs
| Weight | 61 lbs |
|---|---|
| Dimensions | 7.1 × 6.3 in |
| Product Discontinued? | Yes |
| Availability | Discontinued |
| HTS Code | 8507.20.0090 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | thin lead calcium grid |
| Case Material | high modulus polyphenylene oxide |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 1 |
| Battery Nominal DC Volts | 2 |
| Terminal Type | M8 threaded insert |
| Terminal Location | Top |
| Width inches | 7.1 |
| Height inches | 6.3 |
| Depth inches | 13.7 |
| Weight in Lbs | 61 |
| WPC (10min to 1.67vpc @ 25c) | 1763.1 |
| WPC (15min to 1.67vpc @ 25c) | 1442 |
| WPC (20min to 1.67vpc @ 25c) | 1232 |
| 240-cell kW rating (10min) | 423.144 |
| 240-cell kW rating (15min) | 346.08 |
| 240-cell kW rating (20min) | 295.68 |
| AH (c5) | 423.1 |
| AH (c8) | 442.2 |
| AH (c10) | 449.1 |
| AH (c20) | 463.4 |
| 50% DOD Cycle rating | 2050 |
| Capacity Bracket (10 Min WPC) | 1665 – 1964 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 1365 – 1664 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 1065 – 1364 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 350 – 499 Ah (C8) |
| Capacity Bracket (C8 Ah) | 350 – 499 Ah (C8) |
| Capacity Bracket (C10 Ah) | 350 – 499 Ah (C10) |
| Capacity Bracket (C20 Ah) | 350 – 499 Ah (C20) |
| Ambient Temp. Resilience | Moderately Elevated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | Medium Rate |
| Battery Cycle Class | Medium Cycle |
| Cycling Resilience | Float Service to Moderate Cycling |
| Common Applications | Telecom |