NVEB120060WC0FA

Lead Acid Flooded Medium Cycle – High Rate Float Service to Occasional Cycling Stationary Batteries, 12V, 0 Ah (c20), Vented Valve, lead selenium low antimony grid plate

Description

(Superseded) EB1260, OGi Block (12V 2 OGi 61 LA) UPS / High Rate Battery, Flooded lead-acid low antimony grid plate, ABS case, 12V with (2) M8 Threaded Insert terminals [161.7 wpc 15min to 1.65vpc @ 20deg C], [63.2Ah (c8 to 1.75vpc @ 25deg C), 1.240 S.G.], 10.75″L x 8.03″W x 14.09″H (max ht), 74.7 Lbs

Additional information

Weight 74.7 lbs
Dimensions 10.75 × 8.03 × 14.09 in
Product Discontinued?

Yes

Availability

Superseded by NVEB120060WC0FB

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony grid

Case Material

ABS

Battery Valve Style

Vented

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M8 threaded insert

Terminal Location

Top

Length inches

10.75

Width inches

8.03

Height inches

14.09

Weight in Lbs

74.7

WPC (10min to 1.67vpc @ 25c)

194

WPC (15min to 1.67vpc @ 25c)

161.7

WPC (20min to 1.67vpc @ 25c)

135.8

240-cell kW rating (10min)

46.56

240-cell kW rating (15min)

38.808

240-cell kW rating (20min)

32.592

AH (c5)

56.5

AH (c8)

63.2

AH (c10)

65

Capacity Bracket (10 Min WPC)

180 – 249 WPC (10 min)

Capacity Bracket (15 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (20 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Occasional Cycling

Common Applications

Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control