power.Com HC 124200

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 140.8 Ah (c8), Regulated Valve, lead calcium grid plate

SKU: 104-1020-100800
Category:
Tags: , ,
Brands:

Description

(Superseded by VR12-150 or VR124400) UPS High Rate Battery, Lead Acid AGM, case, 12V with (2) Composite Threaded Insert terminals [572.8 WPC @15 min to 1.67vpc],[Ah (c20), 145Ah (c10), 140.8Ah (c8), S.G.], 19.61″L x 6.97″W x 9.06″H (max ht), 119 Lbs

Additional information

Weight 119 lbs
Dimensions 19.61 × 6.97 × 9.06 in
Product Discontinued?

Yes

Availability

Superseded by VR12-150 or VR124400

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

19.61

Width inches

6.97

Height inches

9.06

Weight in Lbs

119

WPC (10min to 1.67vpc @ 25c)

736.9

WPC (15min to 1.67vpc @ 25c)

572.8

WPC (20min to 1.67vpc @ 25c)

473.1

240-cell kW rating (10min)

176.856

240-cell kW rating (15min)

137.472

240-cell kW rating (20min)

113.544

AH (c5)

134

AH (c8)

140.8

AH (c10)

145

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

525 – 614 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, Electric Utility Switchgear Control, UPS Systems