power.com SB 12V 110

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 116 Ah (c8), Regulated Valve, lead calcium grid plate

Description

(Superseded by VRM12-110) UPS/Telco/SG&C/Emergency Lighting Battery, Lead Acid AGM, case, 12V with (2) Composite Threaded Insert terminals [451.4 WPC @15 min to 1.67vpc],[Ah (c20), 117Ah (c10), 116Ah (c8), S.G.], 19.61″L x 6.97″W x 9.06″H (max ht), 114.6 Lbs

Additional information

Weight 114.6 lbs
Dimensions 19.61 × 6.97 × 9.06 in
Product Discontinued?

Yes

Availability

Superseded by VRM12-110

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

19.61

Width inches

6.97

Height inches

9.06

Weight in Lbs

114.6

WPC (10min to 1.67vpc @ 25c)

566.2

WPC (15min to 1.67vpc @ 25c)

451.4

WPC (20min to 1.67vpc @ 25c)

377.1

240-cell kW rating (10min)

135.888

240-cell kW rating (15min)

108.336

240-cell kW rating (20min)

90.504

AH (c5)

112.5

AH (c8)

116

AH (c10)

117

Capacity Bracket (10 Min WPC)

525 – 614 WPC (10 min)

Capacity Bracket (15 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (20 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Electric Utility Switchgear Control, Telecom