S6V740NG (NonFR)

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 6V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

(Discontinued) UPS High Rate Multi-Cell VRLA Battery “Sprinter” (top terminal), High Tin, Lead Calcium Silver AGM, polypropylene case, 6V with (2) M6 Copper Alloy Threaded Insert terminals [746 WPC @15 min to 1.67vpc], 12.14″L x 6.77″W x 8.78″H (max ht), 68 Lbs

Additional information

Weight 68 lbs
Dimensions 12.14 × 6.77 × 8.78 in
Product Discontinued?

Yes

Availability

Discontinued

HTS Code

8507.20.0030

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

3

Battery Nominal DC Volts

6

Terminal Type

M6 Copper Alloy Threaded Insert

Terminal Location

Top

BCI Reference

4

Length inches

12.14

Width inches

6.77

Height inches

8.78

Weight in Lbs

68

WPC (10min to 1.67vpc @ 25c)

882

WPC (15min to 1.67vpc @ 25c)

746

WPC (20min to 1.67vpc @ 25c)

620

240-cell kW rating (10min)

211.68

240-cell kW rating (15min)

179.04

240-cell kW rating (20min)

148.8

Capacity Bracket (10 Min WPC)

820 – 914 WPC (10 min)

Capacity Bracket (15 Min WPC)

730 – 819 WPC (15 min)

Capacity Bracket (20 Min WPC)

615 – 679 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems