SDH25

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead selenium low antimony flat plate

Description

Switchgear / UPS Single Cell Battery, Flooded Lead Selenium, Styrene acrylonitrile (SAN) case, 2V with (4) Lead w/ copper insert terminals [1956 WPC @15 min to 1.67vpc],[972Ah (c10), 936Ah (c8), 1.240 S.G.], 9.2″L x 8.3″W x 28.1″H (max ht), 161.7 Lbs

Additional information

Weight 161.7 lbs
Dimensions 9.2 × 8.3 × 28.1 in
Product Discontinued?

No

Availability

FOB Italy Only

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony flat

Case Material

Styrene acrylonitrile (SAN)

Battery Valve Style

Vented

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Lead w/ copper insert

Terminal Location

Top

Length inches

9.2

Width inches

8.3

Height inches

28.1

Weight in Lbs

161.7

WPC (10min to 1.67vpc @ 25c)

2202

WPC (15min to 1.67vpc @ 25c)

1956

WPC (20min to 1.67vpc @ 25c)

1750

240-cell kW rating (10min)

528.48

240-cell kW rating (15min)

469.44

240-cell kW rating (20min)

420

AH (c5)

815

AH (c8)

936

AH (c10)

972

Capacity Bracket (10 Min WPC)

1965 – 2264 WPC (10 min)

Capacity Bracket (15 Min WPC)

1665 – 1964 WPC (15 min)

Capacity Bracket (20 Min WPC)

1665 – 1964 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Utility Switchgear and Control