STHP-006-4504-59.5-013

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 4960 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Industrial grade VRLA AGM Modular Battery System, 12VDC, 6 cells arranged in 1 stack(s) of (3) 4-cell compartment painted steel module reference “T-4500HP-4×1500/MODx3”, with each containing polypropylene case cells of model T-4500HP, 9917wpc@15min., 11482wpc@10min, 4960Ah(c20), 4504Ah(c8). Battery system nominal reserve kW ratings: 82.512kWb @5min, 68.892 kWb @10min, 59.502 kWb @15min, [30.852 kWh (c1), 54.048 kWh (c8), 55.56 kWh (c10), 59.52 kWh (c20), 62.208 kWh (c24), based on nominal 2.00VPC], 62.17″W x 48.82″H x 27.99″D, 3998.1 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 3998.1 lbs
Dimensions 62.17 × 62.17 × 48.82 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M8 lead-plated brass insert

Length inches

62.17

Width inches

62.17

Height inches

48.82

Depth inches

27.99

Weight in Lbs

3998.1

WPC (10min to 1.67vpc @ 25c)

11482

WPC (15min to 1.67vpc @ 25c)

9917

240-cell kW rating (10min)

2755.68

240-cell kW rating (15min)

2380.08

AH (c5)

3875

AH (c8)

4504

AH (c10)

4630

AH (c20)

4960

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

5000+ WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control