STHP-012-1600-42.2-013

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 24V, 1760 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Telco/Utility/Industrial/Solar, VRLA AGM Modular Battery System, 24VDC, 12 cells arranged in 1 stack(s) of (3) 4-cell compartment painted steel module reference “T-1600HP-4/MOD”, with each containing polypropylene case cells of model T-1600HP, 3526wpc@15min., 4083wpc@10min, 1760Ah(c20), 1600Ah(c8). Battery system nominal reserve kW ratings: 58.68kWb @5min, 48.996 kWb @10min, 42.312 kWb @15min, [21.936 kWh (c1), 38.4 kWh (c8), 39.6 kWh (c10), 42.24 kWh (c20), 44.1792 kWh (c24), based on nominal 2.00VPC], 30.55″W x 48.82″H x 27.99″D, 2738.1 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 2738.1 lbs
Dimensions 30.55 × 30.55 × 48.82 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

12

Battery Nominal DC Volts

24

Terminal Type

M8 lead-plated brass insert

Length inches

30.55

Width inches

30.55

Height inches

48.82

Depth inches

27.99

Weight in Lbs

2738.1

WPC (10min to 1.67vpc @ 25c)

4083

WPC (15min to 1.67vpc @ 25c)

3526

240-cell kW rating (10min)

979.92

240-cell kW rating (15min)

846.24

AH (c5)

1375

AH (c8)

1600

AH (c10)

1650

AH (c20)

1760

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

4065 – 4364 WPC (10 min)

Capacity Bracket (15 Min WPC)

3465 – 3764 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Capacity Bracket (C20 Ah)

000 – 1, 1, 999 Ah (C20)

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control