STHP-120-2000-528-106

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 240V, 2200 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Utility/Industrial/Solar, VRLA AGM Modular Battery System, 240VDC, 120 cells arranged in 10 stack(s) of (6) 4-cell compartment painted steel module reference “T-2000HP-4×1000/MODx2”, with each containing polypropylene case cells of model T-2000HP, 4408wpc@15min., 5103wpc@10min, 2200Ah(c20), 2000Ah(c8). Battery system nominal reserve kW ratings: 733.44kWb @5min, 612.36 kWb @10min, 528.96 kWb @15min, [274.32 kWh (c1), 480 kWh (c8), 494.4 kWh (c10), 528 kWh (c20), 551.808 kWh (c24), based on nominal 2.00VPC], 315.08″W x 70.08″H x 27.99″D, 37169.9 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 37169.9 lbs
Dimensions 315.08 × 315.08 × 70.08 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

120

Battery Nominal DC Volts

240

Terminal Type

M8 lead-plated brass insert

Length inches

315.08

Width inches

315.08

Height inches

70.08

Depth inches

27.99

Weight in Lbs

37169.9

WPC (10min to 1.67vpc @ 25c)

5103

WPC (15min to 1.67vpc @ 25c)

4408

240-cell kW rating (10min)

1224.72

240-cell kW rating (15min)

1057.92

AH (c5)

1720

AH (c8)

2000

AH (c10)

2060

AH (c20)

2200

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

4365 – 4664 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Commercial Lighting Inverters, Data Center UPS Systems, Utility Switchgear and Control