STHP-180-1360-539-124

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 360V, 1496 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Datacenter/Industrial/Solar, VRLA AGM Modular Battery System, 360VDC, 180 cells arranged in 12 stack(s) of (4) 4-cell compartment painted steel module reference “T-1360HP-4/MOD”, with each containing polypropylene case cells of model T-1360HP, 2997wpc@15min., 3470wpc@10min, 1496Ah(c20), 1360Ah(c8). Battery system nominal reserve kW ratings: 748.08kWb @5min, 624.6 kWb @10min, 539.46 kWb @15min, [279.72 kWh (c1), 489.6 kWh (c8), 504 kWh (c10), 538.56 kWh (c20), 563.328 kWh (c24), based on nominal 2.00VPC], 378.31″W x 63.62″H x 27.99″D, 36707 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 36707 lbs
Dimensions 378.31 × 378.31 × 63.62 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

180

Battery Nominal DC Volts

360

Terminal Type

M8 lead-plated brass insert

Length inches

378.31

Width inches

378.31

Height inches

63.62

Depth inches

27.99

Weight in Lbs

36707

WPC (10min to 1.67vpc @ 25c)

3470

WPC (15min to 1.67vpc @ 25c)

2997

240-cell kW rating (10min)

832.8

240-cell kW rating (15min)

719.28

AH (c5)

1170

AH (c8)

1360

AH (c10)

1400

AH (c20)

1496

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

3465 – 3764 WPC (10 min)

Capacity Bracket (15 Min WPC)

2865 – 3164 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Capacity Bracket (C20 Ah)

000 – 1, 1, 999 Ah (C20)

Capacity Bracket (C100 Ah)

000 – 1, 1, 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems