STHP-240-5504-2909-604

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 480V, 6060 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Datacenter/Industrial/Solar, VRLA AGM Modular Battery System, 480VDC, 240 cells arranged in 60 stack(s) of (4) 4-cell compartment painted steel module reference “T-5500HP-4×1360/MODx4”, with each containing polypropylene case cells of model T-5500HP, 12121wpc@15min., 14034wpc@10min, 6060Ah(c20), 5504Ah(c8). Battery system nominal reserve kW ratings: 4033.92kWb @5min, 3368.16 kWb @10min, 2909.04 kWb @15min, [1508.64 kWh (c1), 2641.92 kWh (c8), 2716.8 kWh (c10), 2908.8 kWh (c20), 3041.28 kWh (c24), based on nominal 2.00VPC], 1895.79″W x 63.62″H x 27.99″D, 195770.5 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 195770.5 lbs
Dimensions 1895.79 × 1895.79 × 63.62 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

240

Battery Nominal DC Volts

480

Terminal Type

M8 lead-plated brass insert

Length inches

1895.79

Width inches

1895.79

Height inches

63.62

Depth inches

27.99

Weight in Lbs

195770.5

WPC (10min to 1.67vpc @ 25c)

14034

WPC (15min to 1.67vpc @ 25c)

12121

240-cell kW rating (10min)

3368.16

240-cell kW rating (15min)

2909.04

AH (c5)

4735

AH (c8)

5504

AH (c10)

5660

AH (c20)

6060

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

5000+ WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems