Description
Switchgear / UPS Single-Cell Flooded Lead-Acid Battery, Lead Selenium Plate, 2V with (8) M10 threaded insert terminals [3038.4Ah (c8), 3244AH (c10) to 1.80vpc @ 20degC], 8.35″L x 22.68″W x 33.35″H (max ht), 506 Lbs
Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead selenium low antimony tubular plate
Switchgear / UPS Single-Cell Flooded Lead-Acid Battery, Lead Selenium Plate, 2V with (8) M10 threaded insert terminals [3038.4Ah (c8), 3244AH (c10) to 1.80vpc @ 20degC], 8.35″L x 22.68″W x 33.35″H (max ht), 506 Lbs
| Weight | 506 lbs |
|---|---|
| Dimensions | 8.35 × 22.68 × 33.35 in |
| Product Discontinued? | Yes |
| Availability | Superseded |
| HTS Code | 8507.20.0090 |
| Battery Chemistry | Lead Acid |
| Battery Composition | Flooded |
| Battery Plate Type | lead selenium low antimony tubular |
| Battery Valve Style | Vented |
| LOI Rating | UL-94-V0-or-UL-94HB |
| Cells per Battery | 1 |
| Battery Nominal DC Volts | 2 |
| Terminal Type | M10 threaded insert |
| Terminal Location | Top |
| Length inches | 8.35 |
| Width inches | 22.68 |
| Height inches | 33.35 |
| Weight in Lbs | 506 |
| 50% DOD Cycle rating | 2450 |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Low |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Medium Cycle |
| Cycling Resilience | Float Service to Moderate Cycling |
| Common Applications | Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control |