UPS12-350MR

Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 350 watts per cell (wpc15), Regulated Valve, lead-calcium grid plate

Description

(Superseded by UPS12-355PLP) UPS High Rate Multi-Cell VRLA Battery, AGM, Long Life low calcium proprietary fixed orifice alloy pasted grid plate, Polypropylene case, 12V with (2) 1/4-20 UNC (threaded insert) terminals [350 WPC @15 min to 1.67vpc],[93.2Ah (c20), 89.8Ah (c10), 88Ah (c8)], 12.04″L x 6.83″W x 8.06″H (max ht), 67.4 Lbs

Additional information

Weight 67.4 lbs
Dimensions 12.04 × 6.83 × 8.06 in
Product Discontinued?

Yes

Availability

Superseded by UPS12-355PLP

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead-calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4-20 UNC (threaded insert)

Terminal Location

Top

BCI Reference

27

Length inches

12.04

Width inches

6.83

Height inches

8.06

Weight in Lbs

67.4

WPC (10min to 1.67vpc @ 25c)

440

WPC (15min to 1.67vpc @ 25c)

350

WPC (20min to 1.67vpc @ 25c)

289

240-cell kW rating (10min)

105.6

240-cell kW rating (15min)

84

240-cell kW rating (20min)

69.36

AH (c5)

82

AH (c8)

88

AH (c10)

89.8

AH (c20)

93.2

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Capacity Bracket (C20 Ah)

50 – 99 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems