UPS12-355MRF

Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 358.4 watts per cell (wpc15), Regulated Valve, lead-calcium grid plate

Description

(Discontinued) UPS High Rate Multi-Cell VRLA Battery, AGM, Long Life low calcium proprietary fixed orifice alloy pasted grid plate, Polypropylene case, 12V with (2) M6 (threaded insert) terminals [358.4 WPC @15 min to 1.67vpc],[Ah (c20), Ah (c10), Ah (c8)], 20.1″L x 4.3″W x 9.3″H (max ht), 80 Lbs

Additional information

Weight 80 lbs
Dimensions 20.1 × 4.3 × 9.3 in
Product Discontinued?

Yes

Availability

Discontinued

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead-calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M6 (threaded insert)

Terminal Location

Front

BCI Reference

FT-NW-100

Length inches

20.1

Width inches

4.3

Height inches

9.3

Weight in Lbs

80

WPC (10min to 1.67vpc @ 25c)

440.8

WPC (15min to 1.67vpc @ 25c)

358.4

WPC (20min to 1.67vpc @ 25c)

299.7

240-cell kW rating (10min)

105.792

240-cell kW rating (15min)

86.016

240-cell kW rating (20min)

71.928

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems