UPS12-490MRLP

Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 488 watts per cell (wpc15), Regulated Valve, lead-calcium grid plate

Description

(Superseded by UPS12-475MRX) UPS High Rate Multi-Cell VRLA Battery, AGM, Long Life low calcium proprietary fixed orifice alloy pasted grid plate, Polypropylene case, 12V with (2) 1/4-20 UNC (threaded insert) terminals [488 WPC @15 min to 1.67vpc],[118Ah (c20), 111Ah (c10), 109.6Ah (c8)], 13.42″L x 6.8″W x 8.52″H (max ht), 83 Lbs

Additional information

Weight 83 lbs
Dimensions 13.42 × 6.8 × 8.52 in
Product Discontinued?

Yes

Availability

Superseded by UPS12-475MRX

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead-calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4-20 UNC (threaded insert)

Terminal Location

Top

BCI Reference

31

Length inches

13.42

Width inches

6.8

Height inches

8.52

Weight in Lbs

83

WPC (10min to 1.67vpc @ 25c)

607

WPC (15min to 1.67vpc @ 25c)

488

WPC (20min to 1.67vpc @ 25c)

402

240-cell kW rating (10min)

145.68

240-cell kW rating (15min)

117.12

240-cell kW rating (20min)

96.48

AH (c5)

105.5

AH (c8)

109.6

AH (c10)

111

AH (c20)

118

Capacity Bracket (10 Min WPC)

525 – 614 WPC (10 min)

Capacity Bracket (15 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (20 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems