UPS12-630MRX

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 140 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS High Rate Multi-Cell VRLA Battery, AGM, Polypropylene case, 12V with (2) 1/4-20 UNC (threaded insert) terminals [630 WPC @15 min to 1.67vpc],[140Ah (c20), 133Ah (c10), 131.2Ah (c8)], 13.57″L x 6.8″W x 10.93″H (max ht), 116.6 Lbs

Additional information

Weight 116.6 lbs
Dimensions 13.57 × 6.8 × 10.93 in
Product Discontinued?

No

Availability

Available to Asian and European Markets Only

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4-20 UNC (threaded insert)

Terminal Location

Top

BCI Reference

31 (tall)

Length inches

13.57

Width inches

6.8

Height inches

10.93

Weight in Lbs

116.6

WPC (10min to 1.67vpc @ 25c)

808.7

WPC (15min to 1.67vpc @ 25c)

630

WPC (20min to 1.67vpc @ 25c)

512.4

240-cell kW rating (10min)

194.088

240-cell kW rating (15min)

151.2

240-cell kW rating (20min)

122.976

AH (c5)

127.5

AH (c8)

131.2

AH (c10)

133

AH (c20)

140

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems