VH2-2100

Lead Acid Flooded Medium Cycle – High Rate Float Service to Occasional Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Not sold in the US) (18 OSP.XC 2070) Premium, Power Plant/Station/UPS Battery, Flooded Lead Acid, 2V with (6) Composite Threaded Insert terminals [3512 WPC @15 min to 1.67vpc],[2184Ah (c10), 2084.8Ah (c8), 1.27 S.G.], 8.46″L x 15.74″W x 32.08″H (max ht), 358.3 Lbs

Additional information

Weight 358.3 lbs
Dimensions 8.46 × 15.74 × 32.08 in
Product Discontinued?

Yes

Availability

Not sold in the US

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

15.74

Height inches

32.08

Weight in Lbs

358.3

WPC (10min to 1.67vpc @ 25c)

3826.1

WPC (15min to 1.67vpc @ 25c)

3512

WPC (20min to 1.67vpc @ 25c)

3250.8

240-cell kW rating (10min)

918.264

240-cell kW rating (15min)

842.88

240-cell kW rating (20min)

780.192

AH (c5)

1869.5

AH (c8)

2084.8

AH (c10)

2184

Capacity Bracket (10 Min WPC)

3765 – 4064 WPC (10 min)

Capacity Bracket (15 Min WPC)

3465 – 3764 WPC (15 min)

Capacity Bracket (20 Min WPC)

3165 – 3464 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Occasional Cycling

Common Applications

Data Center, Power Plant Turbine Starting, Utility Switchgear and Control