VL2-620

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium low antimony tubular plate

Description

Solar/Security/Switchgear/Telco, DinRef: (6 OPzS 420), Battery, Flooded Tubular Plate, case, 2V with (2) Composite Threaded Insert terminals [620Ah (c100), 468Ah (c10), 1.24 S.G.], 5.78″L x 8.18″W x 21.06″H (max ht), 75.8 Lbs

Additional information

Weight 75.8 lbs
Dimensions 5.78 × 8.18 × 21.06 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony tubular

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

5.78

Width inches

8.18

Height inches

21.06

Weight in Lbs

75.8

WPC (10min to 1.67vpc @ 25c)

943.6

WPC (15min to 1.67vpc @ 25c)

866.2

WPC (20min to 1.67vpc @ 25c)

800.8

240-cell kW rating (10min)

226.464

240-cell kW rating (15min)

207.888

240-cell kW rating (20min)

192.192

AH (c5)

431

AH (c8)

475

AH (c10)

494

Capacity Bracket (10 Min WPC)

915 – 989 WPC (10 min)

Capacity Bracket (15 Min WPC)

820 – 914 WPC (15 min)

Capacity Bracket (20 Min WPC)

730 – 819 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control