VX2-1600

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, pure lead plante plate

Description

(16 GroE 1600) Premium, Power Plant/Station/UPS Battery, Pure Lead – Planté, 2V with (6) Composite Threaded Insert terminals [3977.8 WPC @15 min to 1.67vpc],[1854Ah (c10), 1788Ah (c8), 1.22 S.G.], 12.99″L x 17.32″W x 23.23″H (max ht), 489.4 Lbs

Additional information

Weight 489.4 lbs
Dimensions 12.99 × 17.32 × 23.23 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

pure lead plante

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

12.99

Width inches

17.32

Height inches

23.23

Weight in Lbs

489.4

WPC (10min to 1.67vpc @ 25c)

4449.5

WPC (15min to 1.67vpc @ 25c)

3977.8

WPC (20min to 1.67vpc @ 25c)

3583.7

240-cell kW rating (10min)

1067.88

240-cell kW rating (15min)

954.672

240-cell kW rating (20min)

860.088

AH (c5)

1648

AH (c8)

1788

AH (c10)

1854

Capacity Bracket (10 Min WPC)

4365 – 4664 WPC (10 min)

Capacity Bracket (15 Min WPC)

3765 – 4064 WPC (15 min)

Capacity Bracket (20 Min WPC)

3465 – 3764 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Power Plant Generating Station, Utility Switchgear and Control