XT4J-9-P

Lead-Acid Flooded Float Service Standby – High Rate limited cycle Stationary Batteries, 8V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

(Superseded by 4JC-07HP) UPS High Rate Multi-Cell Flooded Lead-Acid Battery, Lead Calcium Plate, Polycarbonate case, 8V with (2) Lead Alloy Flag Post terminals [489 WPC @15 min to 1.67vpc],[144Ah (c8), 1.215 S.G.], 10.28″L x 10″W x 14.81″H (max ht), 129 Lbs

Additional information

Weight 129 lbs
Dimensions 10.28 × 10 × 14.81 in
Product Discontinued?

Yes

Availability

Superseded by 4JC-07HP

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

Polycarbonate

Battery Valve Style

Vented

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

4

Battery Nominal DC Volts

8

Terminal Type

Lead Alloy Flag Post

Terminal Location

Top

Length inches

10.28

Width inches

10

Height inches

14.81

Weight in Lbs

129

WPC (10min to 1.67vpc @ 25c)

577

WPC (15min to 1.67vpc @ 25c)

489

WPC (20min to 1.67vpc @ 25c)

423

240-cell kW rating (10min)

138.48

240-cell kW rating (15min)

117.36

240-cell kW rating (20min)

101.52

AH (c5)

135

AH (c8)

144

Capacity Bracket (10 Min WPC)

525 – 614 WPC (10 min)

Capacity Bracket (15 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (20 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems