XT1LC-29-S

Lead-Acid Flooded Float Service Standby – High Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

(Special Order Only, consider 2XTHC-29-S) UPS High Rate Single-Cell Flooded Lead-Acid Battery, Lead Calcium Plate, Styrene-acryllonitrile (SAN) case, 2V with (4) 1″ square dual bolt copper inserted post terminals [4213 WPC @15 min to 1.67vpc, 1.250 S.G.], 7.62″L x 14.12″W x 22.75″H (max ht), 259 Lbs

Additional information

Weight 259 lbs
Dimensions 7.62 × 14.12 × 22.75 in
Product Discontinued?

Yes

Availability

consider 2XTHC-29-S, Special Order Only

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

Styrene-acryllonitrile (SAN)

Battery Valve Style

Vented

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

1" square dual bolt copper inserted post

Terminal Location

Top

Length inches

7.62

Width inches

14.12

Height inches

22.75

Weight in Lbs

259

WPC (10min to 1.67vpc @ 25c)

4697

WPC (15min to 1.67vpc @ 25c)

4213

WPC (20min to 1.67vpc @ 25c)

3807

240-cell kW rating (10min)

1127.28

240-cell kW rating (15min)

1011.12

240-cell kW rating (20min)

913.68

Capacity Bracket (10 Min WPC)

4665 – 4999 WPC (10 min)

Capacity Bracket (15 Min WPC)

4065 – 4364 WPC (15 min)

Capacity Bracket (20 Min WPC)

3765 – 4064 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems