HR3500ET

Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS High Rate Multi-Cell VRLA Battery, Lead Calcium AGM, 12V with (2) 1/4-20 Threaded Studs (posts) terminals [370 WPC @15 min to 1.67vpc],[Ah (c20), Ah (c10), Ah (c8)], 20.13″L x 4.33″W x 9.38″H (max ht), 80 Lbs

Additional information

Weight 80 lbs
Dimensions 20.13 × 4.33 × 9.38 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4-20 Threaded Studs (posts)

Terminal Location

Front

BCI Reference

FT-NW-100

Length inches

20.13

Width inches

4.33

Height inches

9.38

Weight in Lbs

80

WPC (10min to 1.67vpc @ 25c)

472

WPC (15min to 1.67vpc @ 25c)

370

WPC (20min to 1.67vpc @ 25c)

306

240-cell kW rating (10min)

113.28

240-cell kW rating (15min)

88.8

240-cell kW rating (20min)

73.44

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems