60AVR75-15 (NIL)M6-025

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 120V, 640 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate battery string using multiple single cells contained in steel stackable modules, Lead Calcium VRLA AGM, 120vdc battery system [1009 WPC @15 min to 1.67vpc],[640Ah (c20), 570Ah (c10), 552Ah (c8)], 24.5″D x 74″W x 44.2″H (max ht), 5990 Lbs

Additional information

Weight 5990 lbs
Dimensions 74 × 74 × 44.2 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

60

Battery Nominal DC Volts

120

Terminal Location

Front

Length inches

74

Width inches

74

Height inches

44.2

Depth inches

24.5

Weight in Lbs

5990

WPC (10min to 1.67vpc @ 25c)

1042

WPC (15min to 1.67vpc @ 25c)

1009

WPC (20min to 1.67vpc @ 25c)

921

240-cell kW rating (10min)

250.08

240-cell kW rating (15min)

242.16

240-cell kW rating (20min)

221.04

AH (c5)

490

AH (c8)

552

AH (c10)

570

AH (c20)

640

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

990 – 1064 WPC (10 min)

Capacity Bracket (15 Min WPC)

990 – 1064 WPC (15 min)

Capacity Bracket (20 Min WPC)

915 – 989 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Commercial Lighting Inverters, Data Center UPS Systems, Utility Switchgear and Control