NPX-135R (EnerSys)

Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 33 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS High Rate Multi-Cell VRLA Battery, Lead Calcium AGM, ABS Resin case, 12V with (2) M5 threaded insert terminals [135 WPC @15 min to 1.67vpc],[33Ah (c20)], 7.76″L x 5.16″W x 6.22″H (max ht), 26.32 Lbs

Additional information

Weight 26.32 lbs
Dimensions 7.76 × 5.16 × 6.22 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

ABS Resin

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M5 threaded insert

Terminal Location

Top

Length inches

7.76

Width inches

5.16

Height inches

6.22

Weight in Lbs

26.32

WPC (10min to 1.67vpc @ 25c)

172

WPC (15min to 1.67vpc @ 25c)

135

WPC (20min to 1.67vpc @ 25c)

105

240-cell kW rating (10min)

41.28

240-cell kW rating (15min)

32.4

240-cell kW rating (20min)

25.2

AH (c20)

33

Capacity Bracket (10 Min WPC)

130 – 179 WPC (10 min)

Capacity Bracket (15 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (20 Min WPC)

90 – 129 WPC (15 min)

Capacity Bracket (C20 Ah)

20 – 49 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems