DDm85-21

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, Polypropylene case, 2V with (4) Threaded Copper Insert terminals per cell [1757 WPC @15 min to 1.67vpc],[870Ah (c10), 864Ah (c8)] 8.4″L x 8.4″W x 6.5″H (max ht), 142 Lbs

Additional information

Weight 142 lbs
Dimensions 8.4 × 8.4 × 6.5 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

8.4

Width inches

8.4

Height inches

6.5

Depth inches

21.8

Weight in Lbs

142

WPC (10min to 1.67vpc @ 25c)

1942

WPC (15min to 1.67vpc @ 25c)

1757

WPC (20min to 1.67vpc @ 25c)

1605

240-cell kW rating (10min)

466.08

240-cell kW rating (15min)

421.68

240-cell kW rating (20min)

385.2

AH (c5)

790

AH (c8)

864

AH (c10)

870

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1665 – 1964 WPC (15 min)

Capacity Bracket (20 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control