6-DDm100-21 (4-Cell Modules)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Control/Solar VRLA Modular Battery String, Lead Calcium AGM, configured as 1 stack of 2 modules, each module w/ (4) VRLA series-connected cells per stackable steel module, Polypropylene case, 12V with (4) Threaded Copper Insert terminals per cell [1995 WPC @15 min to 1.67vpc],[1040Ah (c10), 1008Ah (c8)] 37.15″W x 26.25″D x 26.26″H (max ht), 1110 Lbs

Additional information

Weight 1110 lbs
Dimensions 37.15 × 37.15 × 26.26 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

37.15

Width inches

37.15

Height inches

26.26

Depth inches

26.25

Weight in Lbs

1110

WPC (10min to 1.67vpc @ 25c)

2201

WPC (15min to 1.67vpc @ 25c)

1995

WPC (20min to 1.67vpc @ 25c)

1827

240-cell kW rating (10min)

528.24

240-cell kW rating (15min)

478.8

240-cell kW rating (20min)

438.48

AH (c5)

920

AH (c8)

1008

AH (c10)

1040

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1965 – 2264 WPC (10 min)

Capacity Bracket (15 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (20 Min WPC)

1665 – 1964 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control