2DXC-19B (san)

Lead-Acid Flooded Float Service Standby – High Rate limited cycle Stationary Batteries, 4V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

UPS / Switchgear & Control – High Rate Multi-Cell Flooded Lead-Acid Battery, Lead Calcium Flat Plate, styrene-acrylonitrile case, 4V with (4) Square Lead-plated copper post terminals [2693 WPC @15 min to 1.67vpc, 1.250 S.G.], 9.5″L x 16″W x 22.68″H (max ht), 353 Lbs

Additional information

Weight 353 lbs
Dimensions 9.5 × 16 × 22.68 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

styrene-acrylonitrile

Battery Valve Style

Vented

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

2

Battery Nominal DC Volts

4

Terminal Type

Square Lead-plated copper post

Terminal Location

Top

Length inches

9.5

Width inches

16

Height inches

22.68

Weight in Lbs

353

WPC (15min to 1.67vpc @ 25c)

2693

240-cell kW rating (15min)

646.32

Capacity Bracket (15 Min WPC)

2565 – 2864 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Utility Switchgear and Control