11 OSP.HC 385

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Superseded by VM2-440) (11 OSP.HC 385) Premium, Power Plant/UPS/Railway Battery, Flooded Lead Acid, 2V with (2) Composite Threaded Insert terminals [1159.7 WPC @15 min to 1.67vpc],[454Ah (c10), 408.8Ah (c8), 1.24 S.G.], 7.44″L x 8.19″W x 16.54″H (max ht), 78 Lbs

Additional information

Weight 78 lbs
Dimensions 7.44 × 8.19 × 16.54 in
Product Discontinued?

Yes

Availability

Superseded by VM2-440

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

7.44

Width inches

8.19

Height inches

16.54

Weight in Lbs

78

WPC (10min to 1.67vpc @ 25c)

1413.6

WPC (15min to 1.67vpc @ 25c)

1159.7

WPC (20min to 1.67vpc @ 25c)

990.2

240-cell kW rating (10min)

339.264

240-cell kW rating (15min)

278.328

240-cell kW rating (20min)

237.648

AH (c5)

367.5

AH (c8)

408.8

AH (c10)

454

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

990 – 1064 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable