8 OSP.HC 680

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Superseded by VM2-720) (8 OSP.HC 680) Premium, Power Plant/UPS/Railway Battery, Flooded Lead Acid, 2V with (2) Composite Threaded Insert terminals [1450.3 WPC @15 min to 1.67vpc],[740Ah (c10), 706.4Ah (c8), 1.24 S.G.], 5.79″L x 8.19″W x 27.95″H (max ht), 117.5 Lbs

Additional information

Weight 117.5 lbs
Dimensions 5.79 × 8.19 × 27.95 in
Product Discontinued?

Yes

Availability

Superseded by VM2-720

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

5.79

Width inches

8.19

Height inches

27.95

Weight in Lbs

117.5

WPC (10min to 1.67vpc @ 25c)

1568.4

WPC (15min to 1.67vpc @ 25c)

1450.3

WPC (20min to 1.67vpc @ 25c)

1344.6

240-cell kW rating (10min)

376.416

240-cell kW rating (15min)

348.072

240-cell kW rating (20min)

322.704

AH (c5)

633.5

AH (c8)

706.4

AH (c10)

740

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable