18 OSP.HC 1890

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Superseded by VM2-1920) (18 OSP.HC 1890) Premium, Power Plant/UPS/Railway Battery, Flooded Lead Acid, 2V with (6) Composite Threaded Insert terminals [3321.1 WPC @15 min to 1.67vpc],[1998Ah (c10), 1928Ah (c8), 1.24 S.G.], 8.46″L x 15.75″W x 32.09″H (max ht), 354.1 Lbs

Additional information

Weight 354.1 lbs
Dimensions 8.46 × 15.75 × 32.09 in
Product Discontinued?

Yes

Availability

Superseded by VM2-1920

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

15.75

Height inches

32.09

Weight in Lbs

354.1

WPC (10min to 1.67vpc @ 25c)

3565.2

WPC (15min to 1.67vpc @ 25c)

3321.1

WPC (20min to 1.67vpc @ 25c)

3105.4

240-cell kW rating (10min)

855.648

240-cell kW rating (15min)

797.064

240-cell kW rating (20min)

745.296

AH (c5)

1756

AH (c8)

1928

AH (c10)

1998

Capacity Bracket (10 Min WPC)

3465 – 3764 WPC (10 min)

Capacity Bracket (15 Min WPC)

3165 – 3464 WPC (15 min)

Capacity Bracket (20 Min WPC)

2865 – 3164 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable