VM2-810

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Occasional Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium low antimony grid plate

Description

Premium, Power Plant/UPS/Railway, DinRef: (9 OSP.HC 765), Battery, Flooded Lead Acid, case, 2V with (4) Composite Threaded Insert terminals [807Ah (c10), 1.24 S.G.], 8.46″L x 7.6″W x 27.95″H (max ht), 146.2 Lbs

Additional information

Weight 146.2 lbs
Dimensions 8.46 × 7.6 × 27.95 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony grid

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

7.6

Height inches

27.95

Weight in Lbs

146.2

WPC (10min to 1.67vpc @ 25c)

1764.4

WPC (15min to 1.67vpc @ 25c)

1632.6

WPC (20min to 1.67vpc @ 25c)

1511.4

240-cell kW rating (10min)

423.456

240-cell kW rating (15min)

391.824

240-cell kW rating (20min)

362.736

AH (c5)

716

AH (c8)

794.4

AH (c10)

831

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Occasional Cycling

Common Applications

Industrial Renewable