XHRL12360WFR

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS High Rate Battery, Lead Calcium AGM, ABS Resin case, 12V with (2) M6 Threaded Insert terminals [372.7 WPC @15 min to 1.67vpc], 10.28″L x 6.63″W x 8.41″H (max ht), 62.37 Lbs

Additional information

Weight 62.37 lbs
Dimensions 10.28 × 6.63 × 8.41 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

ABS Resin

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M6 Threaded Insert

Terminal Location

Top

BCI Reference

24

Length inches

10.28

Width inches

6.63

Height inches

8.41

Weight in Lbs

62.37

WPC (10min to 1.67vpc @ 25c)

477.3

WPC (15min to 1.67vpc @ 25c)

372.7

WPC (20min to 1.67vpc @ 25c)

299.8

240-cell kW rating (10min)

114.552

240-cell kW rating (15min)

89.448

240-cell kW rating (20min)

71.952

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems