LOP12-88-FR

Lead Acid GEL Hybrid Deep Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Outside Plant Battery, Hybrid GEL, ABS case, 12V with (2) T6 (Female M6) Top terminals [281.6 WPC @15 min to 1.67vpc, 90Ah (c10)], 12.05″L x 6.61″W x 8.15″H (max ht), 60.19 Lbs

Additional information

Weight 60.19 lbs
Dimensions 12.05 × 6.61 × 8.15 in
Product Discontinued?

No

Availability

Made to Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

GEL Hybrid

Battery Plate Type

lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

T6 (Female M6)

Terminal Location

Top

BCI Reference

27

Length inches

12.05

Width inches

6.61

Height inches

8.15

Weight in Lbs

60.19

WPC (15min to 1.67vpc @ 25c)

281.6

WPC (20min to 1.67vpc @ 25c)

222.5

240-cell kW rating (15min)

67.584

240-cell kW rating (20min)

53.4

AH (c10)

90

Capacity Bracket (15 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (20 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Ambient Temp. Resilience

Moderately Elevated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Deep Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Broadband CATV Network