Description
(12 OPzS 1500 LA) Telco / Utility / Signaling Single-Cell Battery, Flooded Lead Antimony, Long Rate, Styrene acrylonitrile (SAN) case, 2V with (4) M10 Threaded Insert terminals [1648Ah (c8)], 8.3″L x 10.8″W x 33.9″H (max ht), 249.1 Lbs
Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 1870 Ah (c20), Vented Valve, lead calcium tubular plate
(12 OPzS 1500 LA) Telco / Utility / Signaling Single-Cell Battery, Flooded Lead Antimony, Long Rate, Styrene acrylonitrile (SAN) case, 2V with (4) M10 Threaded Insert terminals [1648Ah (c8)], 8.3″L x 10.8″W x 33.9″H (max ht), 249.1 Lbs
| Weight | 249.1 lbs |
|---|---|
| Dimensions | 8.3 × 10.8 × 33.9 in |
| Product Discontinued? | No |
| Availability | FOB Italy Only |
| HTS Code | 8507.20.0090 |
| Battery Chemistry | Lead Acid |
| Battery Composition | Flooded |
| Battery Plate Type | lead calcium tubular |
| Case Material | Styrene acrylonitrile (SAN) |
| Battery Valve Style | Vented |
| LOI Rating | UL-94-V0-or-UL-94HB |
| Cells per Battery | 1 |
| Battery Nominal DC Volts | 2 |
| Terminal Type | M10 threaded insert |
| Terminal Location | Top |
| Length inches | 8.3 |
| Width inches | 10.8 |
| Height inches | 33.9 |
| Weight in Lbs | 249.1 |
| AH (c5) | 1440 |
| AH (c8) | 1648 |
| AH (c10) | 1740 |
| AH (c20) | 1870 |
| 50% DOD Cycle rating | 1750 |
| Capacity Bracket (C5 Ah) | 000 – 1, 1, 999 Ah (C8) |
| Capacity Bracket (C8 Ah) | 000 – 1, 1, 999 Ah (C8) |
| Capacity Bracket (C10 Ah) | 000 – 1, 1, 999 Ah (C10) |
| Capacity Bracket (C20 Ah) | 000 – 1, 1, 999 Ah (C20) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Low |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Medium Cycle |
| Cycling Resilience | Float Service to Moderate Cycling |
| Common Applications | Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control |