M87-012-05005-R23xxU

Lead Acid AGM Float Service Standby – Ultra High Rate limited cycle Stationary Batteries, 24V, 120 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte 23″ Rack Mount GP Series Ultra-High Rate [connectors sized for 204A or less continuous current] Cellular Station Modular Battery String configured as 1 stack of 2 modules, ea module w/ (6) VRLA series-connected cells per 23″ rack-mount stackable steel module, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 24V, [WPC rates to 1.67 VPC: 341 WPC @5 min, 286 WPC @10 min, 241 WPC @15 min, 209 WPC @20 min, 186 WPC @25 min, 168 WPC @30 min, 133 WPC @45 min, 112 WPC @60 min],[104Ah (c8 / 1.75vpc)], 24.31″W x 12.98″H (max ht) x 15.15″D, 264 Lbs

Additional information

Weight 264 lbs
Dimensions 24.31 × 12.98 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

12

Battery Nominal DC Volts

24

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

24.31

Height inches

12.98

Depth inches

15.15

Weight in Lbs

264

WPC (10min to 1.67vpc @ 25c)

286

WPC (15min to 1.67vpc @ 25c)

241

WPC (20min to 1.67vpc @ 25c)

209

240-cell kW rating (10min)

68.64

240-cell kW rating (15min)

57.84

240-cell kW rating (20min)

50.16

AH (c5)

90

AH (c8)

104

AH (c10)

110

AH (c20)

120

Capacity Bracket (10 Min WPC)

250 – 324 WPC (10 min)

Capacity Bracket (15 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (20 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Capacity Bracket (C100 Ah)

100 – 199 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Ultra High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control