M87-060-GX2000-056xxHV

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 120V, 243.78 kWB (15 min), Regulated Valve, lead calcium grid plate

Description

Absolyte GX Series High Rate [connectors sized for 2672A or less continuous current], (2-GX2000 (FR) modules), SG&C / UPS / Emergency Lighting Modular Battery String configured as 5 stacks of 6 modules, ea module w/ (2) VRLA series-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 120V, [WPC rates to 1.67 VPC: 4462 WPC @10 min, 4063 WPC @15 min, 3710 WPC @20 min, 3405 WPC @25 min, 3145 WPC @30 min, 2567 WPC @45 min, 2184 WPC @60 min],[2000Ah (c8 / 1.75vpc)], 190.45″W x 72.76″H (max ht) x 21.36″D, 20850 Lbs

Additional information

Weight 20850 lbs
Dimensions 190.45 × 72.76 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

60

Battery Nominal DC Volts

120

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

190.45

Height inches

72.76

Depth inches

21.36

Weight in Lbs

20850

WPC (10min to 1.67vpc @ 25c)

4462

WPC (15min to 1.67vpc @ 25c)

4063

WPC (20min to 1.67vpc @ 25c)

3710

240-cell kW rating (10min)

1070.88

240-cell kW rating (15min)

975.12

240-cell kW rating (20min)

890.4

AH (c5)

1810

AH (c8)

2000

AH (c10)

2080

Capacity Bracket (10 Min WPC)

4365 – 4664 WPC (10 min)

Capacity Bracket (15 Min WPC)

3765 – 4064 WPC (15 min)

Capacity Bracket (20 Min WPC)

3465 – 3764 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems