STHP-060-304-39.6-035

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 120V, 330 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Utility/Industrial/Solar, VRLA AGM Modular Battery System, 120VDC, 60 cells arranged in 3 stack(s) of (5) 4-cell compartment painted steel module reference “T-300HP-4/MOD”, with each containing polypropylene case cells of model T-300HP, 661wpc@15min., 765wpc@10min, 330Ah(c20), 304Ah(c8). Battery system nominal reserve kW ratings: 55.02kWb @5min, 45.9 kWb @10min, 39.66 kWb @15min, [20.52 kWh (c1), 36.48 kWh (c8), 37.2 kWh (c10), 39.6 kWh (c20), 41.472 kWh (c24), based on nominal 2.00VPC], 92.44″W x 38.46″H x 17.32″D, 3042.4 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 3042.4 lbs
Dimensions 92.44 × 92.44 × 38.46 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

60

Battery Nominal DC Volts

120

Terminal Type

M8 lead-plated brass insert

Length inches

92.44

Width inches

92.44

Height inches

38.46

Depth inches

17.32

Weight in Lbs

3042.4

WPC (10min to 1.67vpc @ 25c)

765

WPC (15min to 1.67vpc @ 25c)

661

240-cell kW rating (10min)

183.6

240-cell kW rating (15min)

158.64

AH (c5)

260

AH (c8)

304

AH (c10)

310

AH (c20)

330

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Capacity Bracket (C100 Ah)

350 – 499 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Commercial Lighting Inverters, Data Center UPS Systems, Utility Switchgear and Control