HR12160W-FR

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 46.6875 Ah (c20), Regulated Valve, high porosity pure virgin lead grid plate

Description

High Rate UPS battery, VRLA AGM, ABS case, 12V with (2) M6 threaded insert terminals [188 WPC @10 min, 160 WPC @15 min to 1.67vpc] [46.6875Ah (c20)], 7.76″L x 6.5″W x 6.69″H (max ht), 31.5 Lbs

Additional information

Weight 31.5 lbs
Dimensions 7.76 × 6.5 × 6.69 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

high porosity pure virgin lead grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M6 Threaded Insert

Terminal Location

Top

BCI Reference

U1 (wide)

Length inches

7.76

Width inches

6.5

Height inches

6.69

Weight in Lbs

31.5

WPC (10min to 1.67vpc @ 25c)

188

WPC (15min to 1.67vpc @ 25c)

160

WPC (20min to 1.67vpc @ 25c)

127

240-cell kW rating (10min)

45.12

240-cell kW rating (15min)

38.4

240-cell kW rating (20min)

30.48

AH (c5)

40.5

AH (c20)

46.6875

50% DOD Cycle rating

450

Capacity Bracket (10 Min WPC)

180 – 249 WPC (10 min)

Capacity Bracket (15 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (20 Min WPC)

90 – 129 WPC (15 min)

Capacity Bracket (C5 Ah)

20 – 49 Ah (C8)

Capacity Bracket (C20 Ah)

20 – 49 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems